Solution:
Design Optimization
To minimize structural costs, RAND needed to evaluate
several framing schemes--and fast! By conventional
methods,
an optimization of such a magnitude, along with its
effect on the design and construction process, would
have taken too long to develop. But by using AMECO-17,
time was on RAND's side.

Scheme
A First, the original concept of the building had
to be structurally designed with the help of AMECO-17.
At each floor, the framing had four 40' long shear
walls in the Y-direction and eight 8' long shear walls
in the X- direction (see Fig. 2). Ameco-17 projected
this concept would come in at nearly $13 million in
construction costs (see Fig. 3)

Result:
Better, Stronger, Easier, Faster
AMECO-17 produced a design with the slab thickness
reduced from 9" to 8", and the beam depths decreased
from 30" / 24" to 18". This had the effect of further
increasing the flexibility of the structure in both
directions, and reducing seismic forces by 30%. As
a result, construction costs were reduced to $11,773,265
(see Fig. 5), a savings of $1,130,117 over the original
concept. The adoption of Scheme C had additional benefits
as well:
1)
Faster construction time (simplified core)
2) Eliminated footings for removed walls
3) Simplified construction procedures: flying forms
could be used because of reduced beam depth
Rand
was able to run the three optimization schemes and
produce the final design documents, complete with
reinforcing schedules, lists of materials and their
associated costs, in just 20 days, start to finish.
AMECO-17 allowed the engineering design time to be
substantially reduced from the usual 600 man-hours
to only 35 man-hours. And 15 of the 35 hours were
spent by RAND engineers in meetings with the client
to interpret and explain the design results. That
meant that AMECO-17 had done the job 17 times faster,
and in 96% less time.
It took just 6 hours for a RAND engineer to input
the necessary commands in AMECO-17 to design the tower,
despite it being composed of 3,537 members. (See Fig.
6) That's because with AMECO-17, member sizes did
not have to be given, loads did not have to be manually
calculated, nor did any load cases or combinations
have to be specified. Only concrete strength, loading
parameters and member connectivities were inputted,
as well as minimum dimensions for some members. Once
these inputs were done, AMECO-17 required just a few
additional instructions to produce the other two design
schemes.
Based on these input commands, AMECO-17 generated
the geometry of the structure in 3-D, calculated the
floor dead and live loads on each slab and beam, calculated
the seismic forces, set up loading cases, and through
a continual cyclical process, designed the whole structure
faster than traditional methods or other structural
engineering software.The little time it took AMECO-17
to generate the alternative schemes gave Marathon,
Lavalin and the RAND team ample time to discuss specific
criteria and familiarize themselves with details of
the design process.
|
Scheme
B RAND then began the optimization process. Two of the
40' shear walls were eliminated, the building
redesigned with AMECO-17 and the results reviewed. The
results: a more flexible structure in the Y-direction,
a significant reduction in the seismic force, and a
$600,000 reduction in construction costs. Good, but
RAND and the developers were looking for more. So, they
proceeded to Scheme C.
Scheme C The two 40' shear walls and the eight 8 `shear
walls in the X-direction were eliminated, leaving just
two shear walls (see Fig. 4). In this design run, AMECO-17
was instructed to minimize the slab thickness and the
perimeter beam depth.
 |
Fig. 5 Costruction Costs Chart
|
 |
|
Fig 6 Ameco -17 command input file
|
|